A 16-channel acquisition board connects two eight-channel ADS1299 converters to one SPI bus. The controller reads both status words and sees the expected frame count, yet plots show the channels slowly moving out of alignment. Raising the SPI rate or switching to a daisy chain can reduce the time spent moving data. To establish whether conversions are synchronous, first inspect CLK, START and the two DRDY signals at the converters. A timestamp assigned by the host after reading the data describes a different event.
The two clocks on the schematic have different jobs
CLK is the converter's time base. The modulator runs at half the CLK frequency, and CONFIG1 sets the decimation ratio. In the 500 SPS setting, the resulting rate is fCLK ÷ 4096. Exactly 500 sample sets per second require a 2.048 MHz input. SCLK is the serial clock and sets how fast the host can fetch completed results. With separate chip selects the converters can share SCLK, DIN and DOUT while conversion timing still depends on each device's own CLK and START. If two readings enter the same DMA callback, that callback indicates transfer completion. It places no constraint on the relative conversion time. TI ADS1299 datasheet, CONFIG1 data rate TI multiple converter synchronisation and cascade mode
Suppose two independent oscillators are nominally 2.048 MHz, with one running 0.1% high and the other 0.1% low. The corresponding output rates are 500.5 SPS and 499.5 SPS. Even with the first frames aligned, the timing mismatch is about 0.20 ms after 100 ms and grows to about one 2 ms sample interval after a second. If the host continues to combine samples with the same index, the pairings drift. These figures follow from assumed frequency errors. Use the model to check a measured drift slope or to work backward to the allowable relative frequency error. Two more accurate independent oscillators still need a relative drift budget over the intended observation period.
Once CLK is shared, start both digital filters together
TI's multiple-device diagram distributes CLK and START to both converters and keeps their DRDY outputs separate. One board design uses a single external 2.048 MHz source and sets CLKSEL low on both ADS1299 devices. Another uses the first converter's on-chip oscillator. Set its CLKSEL high and enable CLK_EN in CONFIG1 to drive the CLK pin. Set the second converter's CLKSEL low so that it receives that clock. Both designs give the converters one time base. Absolute sample rate follows the external source in the first design and the source converter's oscillator in the second. Distribute a common START and verify identical data-rate settings before checking alignment at DRDY. TI ADS1299 §10.1.4, Figure 69
When the first ADS1299 supplies the clock, the second device's initialisation should allow for CLK becoming available after power-up. Use a repeatable sequence. Configure the source device to output CLK, confirm that it reaches the receiving device, complete initialisation according to the device requirements, and finally apply a common START. Check pin direction during reset. If the design allows either converter to reset or power down independently, include a source-device restart in the test and verify that the other converter stops and realigns. With an external oscillator, check its startup time, logic levels and actual output availability. A test point near the receiving CLK input helps with either design.
At 500 SPS, TI's START settling table gives 16393 CLK periods for the first fully settled output. At 2.048 MHz this is about 8.004 ms. Later DRDY falling edges occur approximately every 2 ms. A 2 ms timeout for the first DRDY would flag normal filter settling as a failure. Capture START and both DRDY falling edges together, then check whether their relative phase changes over a long record. Later rising edges can depend on SPI activity, so compare the defined data-ready edges when checking synchronisation. TI ADS1299 datasheet, Table 7 and data-ready timing
Once the converters are aligned, budget enough time to read both frames
Consider cascaded readout with individual chip selects. Each eight-channel frame contains a 24-bit status word and eight 24-bit channel words, for 216 bits. Two devices need 432 bits. Reading the raw data at a 1 MHz SCLK takes 432 µs, nominally leaving 1568 µs in a 2 ms sample interval. Allow for chip-select transitions, host response, the update exclusion interval and any settling time in the serial interface specification. Command-based readout adds command overhead. If you later move to a daisy chain, check the timing and frame lengths for the actual devices in the chain rather than carrying over the single-device minimum SCLK. TI's public forum includes a developer asking how to combine independent chip selects with a daisy chain, an example of why readout topology needs a system-level decision. TI ADS1299 SPI SCLK and readout timing TI E2E discussion on multiple-device connections
Use separate limits for relative synchronisation and absolute timing. If a 60-second record must finish within 1 ms of an external standard, the ideal absolute clock budget is 0.001 ÷ 60, or about 16.7 ppm. Reference and trigger uncertainty reduce the allowance available to the acquisition board. Two converters sharing one internal oscillator can stay aligned with one another while drifting together against the outside reference. When the system must synchronise externally, record both the difference between converters and the error against the external standard.
Keep a separate interrupt count and sequence number for each converter during qualification. An apparently complete combined frame can hide a missing record. If DRDY is aligned but only one stream has a sequence gap, check which device was selected and whether a read crossed the next update. If both data-ready lines remain continuous and individually regular while moving apart, return to the CLK routing and the actual source. Preserve per-device sample numbers in the fixture so a missing read can be traced from the data file to the scope record.
The sourcing record should say whether 2.048 MHz refers to a powered external oscillator or to the onboard oscillator in the first ADC. For an external source, check the receiving thresholds at the chosen DVDD, duty cycle, load, startup time and frequency error over the operating temperature range. If both converters need long-term phase alignment and the acquisition also needs to agree with another instrument, convert the allowed cross-instrument time difference and record duration to a clock accuracy requirement. Finally, apply the same bench-generated signal to both analogue inputs and verify alignment in the recorded data. Retain the raw DRDY traces and both status words so that dropped reads, clock drift and analogue filter differences can be diagnosed from separate evidence.