Two drives share a CANopen bus. A scope shows a synchronization frame every millisecond, but the left and right actuators sometimes move at different times. Before specifying a tighter oscillator, identify what the drives synchronize. A SYNC frame gives nodes a shared periodic event. A drive can use that event to transmit status, consume a command, or update motor output according to its object configuration and execution logic. Frame period alone does not establish the timing of mechanical motion.
CAN in Automation explains SYNC in terms of frame cycles and synchronous process data objects, or PDOs. PDOs commonly carry commands and status. A device can be configured to transmit a PDO after a specified number of SYNC events, for example to distribute bus load or schedule processing. Receiving devices can apply commands at distinct times. Check the CANopen version, device description, and application manual. A visible SYNC counter does not define the actual drive behavior.
Put frame transmission, command application, and movement on one timeline
Assume a 1 ms SYNC period. Drive A updates a software status on every event and drive B sends a status PDO every second event. Treating both status streams as movement measurements makes B report half as often and sometimes seem 1 ms late. That difference may be reporting cadence alone. Suppose the drive documentation says a synchronized command enters a local control task. With a 250 µs task interval, different local task phases can apply the same command at different times. These numbers illustrate the timeline. Determine actual delays from the manufacturer and measurement.
Bus traffic matters as well. A PDO can be queued for transmission or wait behind a frame already on the bus. Capture SYNC, command frame, drive status or marker output, and encoder feedback together. If the command is already late on the bus, check configuration and traffic load. If both drives receive the same target in the same cycle but motion diverges, check local tasks, state machines, and mechanics. Ramp rates, limits, or braking conditions can differ even while both transceivers run at the correct baud rate.
Estimate the oscillator effect for comparison. With a hypothetical 40 ppm relative difference, two free-running oscillators separate by about 40 ns after 1 ms and 40 µs after 1 s. Verify whether tasks lock to SYNC and where local error accumulates. If an observed delay is consistently about one SYNC period, check task and PDO cycle boundaries first. If it grows gradually during operation, measure the local timebases and check how the devices realign to SYNC.
Test command timing and mechanical timing separately
Start with two identical drives and a known safe unloaded setup. Follow the normal operating procedure using the same commands and frame cadence. Look for device timestamps for command receipt, application, and internal cycle transitions. Use a reproducible sensor setup and a common time reference to observe the actual movement. Save raw timestamps, node IDs, configuration, firmware, load, and trigger method. Two local clocks that have not been aligned cannot establish a mechanical delay by direct subtraction. Use a shared instrument or verifiable common reference for the external measurements.
Restore normal bus load and run cold startup, additional unrelated nodes, interruption and resumption of SYNC, and reconnection. Change one condition at a time and check whether the drives rejoin the same cycle. Exercise the expected alarm or action limit when a command is accepted one cycle late. A lightly loaded bench may not reproduce the field issue. Request the manufacturer's instructions for exposing internal state markers if available.
Purchasing can turn "supports CANopen" into verifiable questions about SYNC use, command-to-application delay or its test method, supported synchronous PDO types, and configuration. If the project cares about physical motion, define the event to measure. Engineering can track bus arrival, firmware application, and movement separately.
Some drives can attach a sequence number or application acknowledgment to process data. Under controlled test conditions, send both devices the same sequence and deliver one update late. Observe whether a drive holds the previous value or waits until the next cycle. Check this behavior on a replacement as well as steady-state timing, since a regular SYNC broadcast cannot establish how a device handles a missed update.